Maintenance
Continuous Feed: 2 – 10 ppm BCP 2175
Slug Dose: 25 – 65 ppm BCP 2175
- Dose 1 to 3 times per week.
- Optimize the dosing and frequency of dosing based on quality control (QC) metrics.
Clean-Up
Slug Dose: 50 – 100 ppm BCP 2175
- Dose each day or until system performance measurements and visual inspection show satisfactory removal of organic deposits and system clean-up.
Super Slug Dose (Clean-up of heavily fouled systems): 100 ppm BCP 2175
- Dose at 1-2 hour intervals.
- Add high concentration dose (100 ppm) of BCP 2175 to penetrate and disperse organic deposits from the surfaces.
- After 1-2 hours, initiate an enhanced/manual blow down to remove released organic deposits & non-organic deposits.
- Repeat dose and enhanced/manual blow down steps until system quality control measurements indicate satisfactory clean up.